Added advanced earth cable selection to the Cable Size Calculator


Hi Reader

I am just letting you know.

I worked on the maximum demand calculator for the past six months.

I have now returned to the cable size calculator. I added advanced earth cable selection for single-core cables.

When the earth cable size is selected as "Auto", the selection works as follows:

Step 1: The calculator starts with the minimum recommended earth size from AS/NZS 3000, Table 5.1.

Step 2: The earth cable size is increased if the earth fault current rating is too low.

Step 3: The earth cable size is increased if the earth loop impedance is too high.

In "Auto" the earth size can be increased up the size of the active cable. If you need a larger earth cable, you can still select the earth size manually.

Previously, the calculator did not increase the earth cable size beyond the minimum recommended size. It suggested a larger active-earth cable combination, which was not optimal.

Example of advanced earth cable selection

Click to try.

Please let me know if you have any questions or suggestions.

Adam van Staden
LinkedIn Profile

This information does not constitute legal, professional or commercial advice. JCalc Pty Ltd gives no guarantees, undertakings or warranties in this regard, and does not accept any legal liability or responsibility for the content or the accuracy of the information so provided, or, for any loss or damage caused arising directly or indirectly in connection with reliance on the use of such information.

Subscribe to jCalc updates

One email per month.

Read more from Subscribe to jCalc updates

Hi Reader Just letting you know. I have changed the mobile layout of the Maximum Demand Calculator. See the images below. I also made a few improvements and fixed some defects. Improvements I added kW ratings. You now have A, Watt and kW. I added 3-phase loads to Blocks of Living Units. I improved the descriptions for the default loads when you open the calculator the first time. I updated the example in the content below the calculator with more load groups and more detailed calculation...

Hi Reader I am just letting you know. I added electrode images to the Arc Flash Calculator. Plus a few other improvements. 1. Electrode images 2. Model limit validations I added the IEEE-1584 model limitations to the field validations, including voltage, conductor gap and enclosure size. For example: 2. Simplified equipment types I reduced and simplified the list of typical equipment types. They are used to prefill the working distance, conductor gap and enclosure dimensions with typical...

Hi Reader I am just letting you know. I made a few small improvements and fixed defects on the Cable Size Calculator. Improvements I added a confirmation window for the reset button. I added a warning for the user to raise the ambient temperature for cables installed in ceilings. I added step-by-step calculations for the phase and earth fault at load. I improved the step-by-step calculations for maximum earth loop distance. I added new content to explain maximum loop distance calculations. I...